Residential apartments in Newcastle's inner-city Wickham precinct, with ground-floor storage and services areas.




One Stop Fire rectified the fire dampers serving the ground-floor storage relief and comms supply ductwork and the Level 2 lobby riser, verifying each against AS/NZS 1668.1 and AS 1530.4 for blade operation, seating in the wall, flange and seating angles, perimeter fire seal, breakaway connection to AS 1682.2 and correctly formed penetration.
Category
Strata Residential
Location
Wickham, NSW
Scope
Residential apartments in Newcastle's inner-city Wickham precinct, with ground-floor storage and services areas.
More passive fire protection work delivered across commercial, strata and industrial buildings.